Ct-7000 operating instructions – Vanguard CT-7000 User Manual
Page 28
CT-7000 Operating Instructions
21
9.1.2 Timing an OPEN Operation With Insertion Resistors
The CT-7000 can time breakers with insertion resistors. The insertion resistor can
range from 10 to 7,000 Ohms. Any insertion resistor more than 7,000 Ohms is detected as
an open circuit. The timing window results will show the main contact time and the insertion
resistor contact time. Graphic reports will show the main contact and the resistor contact
activities on each of the channels.
Table 5.0 Open Operation With Insertion Resistor
STEP
OPERATION
ACTION
DISPLAY
1
READY TIMER FOR BREAKER OPERATION.
PRESS #1 KEY.
INSERTION RESISTOR?
1.NO
2.YES
2
SELECT INSERTION RESISTOR.
PRESS #2 KEY.
RESISTOR VALUE:
1.LESS THAN 1000 OHM
2.1000 to 2000 OHM
3.MORE THAN 2000 OHM
3
SELECT LESS THAN 1000 OHM RESISTOR
RANGE.
PRESS #1 KEY.
TIMING WINDOWS:
1.WINDOW = 1 SEC
2.WINDOW = 10 SEC
3.WINDOW = 20 SEC
4
SELECT 1-SECOND WINDOW.
PRESS #1 KEY.
TRIGGER MODE:
1. Internal Trigger
2. External Trigger
5
SELECT INTERNAL TRIGGER.
PRESS #1 KEY.
TIMING MODE:
1. OPEN
2. CLOSE
3. O-C
4. C-O
5. O-C-O
6
SELECT OPEN OPERATION.
PRESS #1 KEY.
OPEN TIMING
Hold "ARM" Switch,
Then "START".
"STOP" to ABORT
7
INITIATE OPEN COMMAND.
HOLD THE "ARM"
SWITCH AND
PRESS THE "START" KEY.
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 15 seconds)
8
ANALYZER IS READY TO OUTPUT RESULTS.
NONE.
1.TIME BREAKER
2.GET RESULT
3.SET-UP
4.DIAGNOSTIC
NOTE
The user can set the CT-7000 to print tabulated and graphical reports automatically
after it completes a test. See Paragraph 9.21 for the automatic print setting.