CT-7000 Operating Instructions
29
9.3 Get Graphic Timing Results Using the Thermal Printer
Selecting the “PLOT FULL CHART” command will plot the timing chart as follows:
•
Timing chart from 0 to 1000 ms with one second window and 50 ms time markers.
•
Timing chart from 0 to 10 seconds with 10 second window and 500 ms time markers.
•
Timing chart from 0 to 20 seconds with 20 second window and one second time markers.
Table 9.0 Plot Chart and Tabulated Report
STEP
OPERATION
ACTION
DISPLAY
1
GET TIMING RESULTS.
PRESS #2 KEY.
1. PRINT TEST RESULTS
2. PLOT FULL CHART
3. PLOT EXPANSION
4. PLOT 0-200 MS
2
PLOT FULL CHART.
PRESS #2 KEY.
SELECT PRINTER
1. INTERNAL THERMAL
2. EXTERNAL INK JET
3
SELECT THERMAL PRINTER.
PRESS #1 KEY.
PLEASE WAIT
PLOTTING GRAPH
4
RETURN TO MAIN MENU AFTER PRINT
CHART.
NO ACTION.
1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
NOTE
1. Plot Expansion, which is Selection #3, in Step 1, allows the user to expand the graphic
results in 100 ms increments.
2. Selecting “PLOT 0-200 MS” will automatically plot the timing chart from 0 to 200
milliseconds in the expansion mode with 10 ms timing markers, which can be seen in
Figure 14.0.
3. Graphical result interpretations are shown in Figures 16.0, 17.0 and 18.0.