CT-7000 Operating Instructions
10
7.2 CT-7000 Operating Voltages
The CT-7000 operating voltage is selectable between 110/120 Vac, 50/60 Hz or 220/240
Vac, 50/60 Hz. Voltage selection is set by the JP1 connector on the Power Supply board and the
JP3 connector on the Initiate board of the CT-7000. The jumper settings for the connectors are
shown in Table 3.0.
Table 3.0 Voltage Selection Jumper Setting
VOLTAGE SELECTION
CONNECTOR PIN
110-120 Vac
Pin 1& 2, 3 & 4
220-240 Vac
Pin 2 & 3
An initiate circuit relay with the corresponding operating voltage must also be installed in the
CT-7000 Initiate board.
NOTE
The factory sets the operating voltage.
7.3 CT-7000 Main Power Fuse
The CT-7000 uses an AC input module that contains the AC receptacle, power switch and
protective fuses. The 3 Ampere replacement fuses should be 20mm, 250Vac, fast-blow types.
NOTE
The OPEN and CLOSE initiate are 5 Ampere fuses that should be 3AG, 250Vac,
fast-blow types.
7.4 CT-7000 Printer and Printer Paper
The built-in, thermal printer uses 4.5 inch wide, thermal paper for printing test results. To
maintain the highest, quality printing and to avoid paper jamming, it is highly recommended that
the thermal paper be supplied by the factory. Additional paper can be ordered from either of the
two sources listed below: