Ct-7000 operating instructions – Vanguard CT-7000 User Manual
Page 50
![background image](/manuals/354162/50/background.png)
CT-7000 Operating Instructions
43
9.9 Computer Interface
Each CT-7000 has an RS-232C port, where the Breaker Analysis Software package provided
with each CT-7000, enables an IBM-compatible personal computer to communicate with the unit.
The software operating under Windows 95, 98, Me, 2000, NT and XP environments allow the user
to upload timing shots stored in the EEPROM into the computer. From the user's computer, the
user can now reanalyze the breaker’s timing shots and then output the timing reports through an
office printer. Since timing shots are stored in the office computer, users can create a database
of a breaker's timing history.
Follow the steps in Table 15.0 to put the CT-7000 under computer control:
Table 15.0 Selecting or Aborting Computer Control
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SET UP MENU.
PRESS # 3 KEY.
1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT NEXT PAGE.
PRESS # 4 KEY.
1. SHOT DESCRIPTION
2. COMPUTER ITF
3. SET CLOCK
4. SET PRINT MODE
3
SELECT COMPUTER INTERFACE.
PRESS # 2 KEY.
COMPUTER ITF MODE
"STOP" TO ABORT
NOTES
1. An interconnect cable must be run between the CT-7000’s RS-232C port and an
IBM-compatible PC.
2. Refer to the breaker timing software manual to run the unit remotely from an IBM-
compatible computer.
3. The CT-7000's RS-232 connector pin layout is in the
chart to the right.
4. The operator is required to put the CT-7000 under the
“Computer ITF Mode” before executing the PC
program.
PIN No.
SIGNAL NAME
2
Tx
3
Rx
5
GND