7. Appendices

The maximum allowable power for 4 parallel UPS units is limited to 4 x Pn.

Restrictions to parallel operation

(*) : except in ECO mode or bypass mode.

Thermal characteristics

The operating temperature range is 0°C to +40°C (0°C to 30°C for overload conditions), however optimum operation is within

the +20°C to +25°C range.

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at temperatures under

10°C.

Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation
due to the risk of thermal runaway.

.

Air enters through the bottom.

Air exits through the top.

Single UPS

Parallel UPS

EMC level

Category C3

Category C3

ECO mode

Yes

No

Frequency converter

Yes

Yes (for two UPSs)

Compatibility with the synchronisation module

Yes

Yes

UPS power rating

Heat losses

Recommended air
throughput

20 kVA

2.4 kW

1 332 m

3

/h

30 kVA

3 kW

1 332 m

3

/h

40 kVA

3.4 kW

1 332 m

3

/h

60 kVA

4.9 kW

1 332 m

3

/h

80 kVA

5.8 kW

2 556 m

3

/h

100 kVA

7 kW

2 556 m

3

/h

120 kVA

8.4 kW

2 556 m

3

/h