Restrictions to parallel operation, Thermal characteristics, Appendices – APC GALAXY 5000 User Manual
Page 64

34001813EN/AE
- Page 64
7. Appendices
The maximum allowable power for 4 parallel UPS units is limited to 4 x Pn.
Restrictions to parallel operation
(*) : except in ECO mode or bypass mode.
Thermal characteristics
◗
The operating temperature range is 0°C to +40°C (0°C to 30°C for overload conditions), however optimum operation is within
the +20°C to +25°C range.
◗
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at temperatures under
10°C.
Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation
due to the risk of thermal runaway.
.
Air enters through the bottom.
Air exits through the top.
Single UPS
Parallel UPS
EMC level
Category C3
Category C3
ECO mode
Yes
No
Frequency converter
Yes
Yes (for two UPSs)
Compatibility with the synchronisation module
Yes
Yes
UPS power rating
Heat losses
Recommended air
throughput
20 kVA
2.4 kW
1 332 m
3
/h
30 kVA
3 kW
1 332 m
3
/h
40 kVA
3.4 kW
1 332 m
3
/h
60 kVA
4.9 kW
1 332 m
3
/h
80 kVA
5.8 kW
2 556 m
3
/h
100 kVA
7 kW
2 556 m
3
/h
120 kVA
8.4 kW
2 556 m
3
/h