Maintenance, 1 identification of alarms, 2 life cycle monitoring (lcm) – APC GALAXY 5000 User Manual

Page 50

background image

34001813EN/AE

- Page 50

4. Maintenance

4.1 Identification of alarms

Alarm conditions are identified by LEDs (31), (32), (33) and the buzzer.

Detailed information on all alarms is supplied on the display.
1 - On the screen, select the alarm for which information is required.

2 - Hold down the corresponding function key to display the possible causes of the fault and the required action.

4.2 Life Cycle Monitoring (LCM)

LED (31)

LED (32)

LED (33)

Buzzer

Signification

-

-

Intermittent

Normal AC source not available

-

-

Intermittent

UPS shut down following end of
battery power

-

-

Intermittent

UPS shut down on fault requiring
servicing by after-sales support

The "Life Cycle Monitoring" function provides UPS maintenance advice

to guarantee installation availability for the user.

The display gives 3 messages enabling the following to be identified:

- The end of the contractual legal warranty: "End of warranty check

recommended".
- Regular maintenance requirements and the end of service life for

consumable components: "Technical check recommended".

- The end of the battery service life: "Battery check required".

In addition to these messages, the minor fault LED (32) lights up and the
buzzer sounds.

These messages can be deleted by pressing the function key (35). This

also causes LED (32), to go out, the buzzer to stop and the removal of the
"Global Alarm" remote signalling.

To completely disable LCM indications, use the display to enter the
password required to disable the function.