Installation, 1 location, 2 layout of cabinets – APC GALAXY 5000 User Manual

Page 12: 1 location 2.2 layout of cabinets

background image

34001813EN/AE

- Page 12

2. Installation

2.1 Location

2.2 Layout of cabinets

To ensure correct ventilation, leave nothing
on top of the UPS.

Leave one meter of free space in front of the

UPS for door opening.
The cabinet rests on four cylindrical feet,

40 mm in diameter, positioned in the four

corners of the cabinet to spread the weight.

If 500 mm of free space is not maintained
above the UPS, abnormal temperature rise

may occur.

The UPS must be installed in a room with

restricted access (qualified personnel

only).

(*) The UPS can operate correctly back to the

wall, but it is preferable to leave some space

for easier maintenance.

0 - 600 mm*

I

O

3s

?

~

>500 mm

>1000 mm

I

O

3s

?

~

I

O

3s

?

~

UPS cabinet

UPS cabinet

Battery cabinet

Battery cabinet 2

Battery cabinet 1