Operating mode, Frequency, Automatic bypass – APC GALAXY 5000 User Manual

Page 47: Battery, Operation, Operating mode frequency automatic bypass battery

background image

34001813EN/AE

- Page 47

3. Operation

Operating mode

Frequency

Automatic bypass

Battery

Function

Factory setting

Options

UPS operating mode

NORMAL

ECO

UPS automatic start

Disabled

Enabled

Authorised number of starts

4

1 to 255

Delay before reset of number of

executed automatic starts

4 seconds

1 to 60 seconds

UPS output frequency

50 Hz

60 Hz

Tolerance for Bypass AC source

8 %

0.5 - 1 - 2 - 4 %

Synchronisation speed with Bypass
AC source

2 Hz / s

1 Hz / s

Transfer to Bypass AC source

Enabled

Disabled - disabled when limiting

Transfer to bypass with Bypass AC

source out of tolerances

Enabled

Disabled

Low battery warning threshold if

battery monitor inactive

40% remaining backup time

20 - 60 - 80 % remaining backup time

Low battery warning threshold if
battery monitor active

4 minutes of battery backup time

1 to X minutes of battery backup time

Interval between two battery tests

30 days

1 to 180 days