2. Installation

2.14 Connection of the relay communications card

Isolate and lock-out all power sources for this card before making connections.
Never connect SELV (safety extra low voltage) and non-SELV circuits to the different outputs of the same card.

1 - Remove the cover (52) secured by the screws (50).

2 - Run the communications cables through the cable entry holes (53).

3 - Connect the conductors to the input (55) and output (54)terminal blocks.

4 - Put the cover back in place and secure it with the screws (50).
5 - Tighten the screws (56) to block the cables.

6 - Indicate the locations of the power sources on the labels.

7 - Insert the card in its slot.
8 - Secure the card with two screws (51).

1

2 3

4 5

6

A

B

53

55

54

51

52

51

50

51

56