Communications card connection example, Adding communication cards, Installation – APC GALAXY 5000 User Manual

Page 35

background image

34001813EN/AE

- Page 35

2. Installation

Characteristics of the contacts on the relay communications card.

Communications card connection example

If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from the

upstream source to ensure the safety of personnel working on the installation.

Adding communication cards

Characteristics of the output contacts:
Permissible voltage: 250V AC, 30V DC.

Permissible current: 2 A.

Cable : 4 x 0.93 mm

2

, Ø 6.6 ± 0.3 mm.

Characteristics of the input contacts:

Switched voltage: 5 V DC
Consumption: 10 mA.

Cable: 4 x 0.34 mm

2

, Ø 5 ± 0.5 mm.

UPS OFF

UPS ON

6

5

4

3

2

1

B A

Low battery warning

Load on battery power

Load on automatic bypass

Load on UPS

Battery fault

General alarm

carte de

communication

source

Disconnecting device that can be locked

AC

communication
card

2

4

1

3