Electrical characteristics

Selection of protection devices

UPS short-circuit current with inverter coupled and By-pass AC source out of tolerances:

UPS unit with common normal and Bypass AC inputs

UPS unit with separate normal and Bypass AC inputs

When sizing the upstream circuit breakers, the parameters presented below must be taken into account:

Time/current curves for UPS input and output fuses:

Sn

20 kVA

30 kVA

40 kVA

60 kVA

80 kVA

100 kVA

120 kVA

In

29 A

43 A

58 A

87 A

115 A

144 A

173 A

Limitation

190 A

190 A

190 A

240A

360 A

480 A

480A

14

Q1

16

Q4S

Q5N

15

Normal AC

Bypass AC

Upstream

circuit breaker

(not supplied)

Downstream

circuit breaker

(not supplied)

Output

fuses

Input

fuses

Load

14

Q1

16

Q4S

Q5N

15

Upstream

circuit breaker

(not supplied)

Downstream

circuit breaker

(not supplied)

Normal AC

Bypass AC

Upstream

circuit breaker

(not supplied)

Output

fuses

Input

fuses

Load

10

4

10

3

10

2

10

1

10-

1

10-

2

10-

3

10-

4

10

4

10

3

10

2

10

I (A)

t (s)

80 kVA : 160A

100-120 kVA : 315A

60 kVA : 125A

20-30-40 kVA : 80A