Input / output characteristics, Power supplied as a function of input voltage, Permissible ups overloads as a function of time – APC GALAXY 5000 User Manual
Page 62: Appendices, I/in, P/pn
34001813EN/AE
- Page 62
7. Appendices
Line current values
Input / output characteristics
Normal AC source / Bypass AC source
Load output
Rated power of each
UPS unit
Continuous input
current at U=400V
Input current at
U=400V overload =
1.25 In limited to 10
min.
Input current at
U=400V overload =
1.5 In limited to 1 min.
Input/output fuse
ratings
20 kVA
29 A
36 A
44 A
80 A
30 kVA
43 A
55 A
65 A
80 A
40 kVA
58 A
72 A
87 A
80 A
60 kVA
87 A
108 A
130 A
125 A
80 kVA
115 A
145 A
174 A
160 A
100 kVA
144 A
181 A
217 A
315 A
120 kVA
173 A
217 A
260 A
315 A
Standard UPS
UPS with backfeed
protection
Uin
380 to 443 V
380 to 443 V
Input voltage range permitted by the standard
according to the curve below
250 to 470 V
340 to 470 V
Fin
45 to 65 Hz
45 to 65 Hz
Uout
380 V
400 V
415 V
+ 3%
- 3%
Power supplied as a function of
input voltage
Permissible UPS overloads as a function of time
P/Pn
100%
70%
250V 340V 470V
U
I/In
2,2
2
1,8
1,6
1,4
1,2
1
10
4
10
1
0,1
t (s)
10
5
10
3
10
2
60
600