7. Appendices

Line current values

Input / output characteristics

Normal AC source / Bypass AC source

Load output

Rated power of each
UPS unit

Continuous input
current at U=400V

Input current at
U=400V overload =

1.25 In limited to 10

min.

Input current at
U=400V overload =

1.5 In limited to 1 min.

Input/output fuse
ratings

20 kVA

29 A

36 A

44 A

80 A

30 kVA

43 A

55 A

65 A

80 A

40 kVA

58 A

72 A

87 A

80 A

60 kVA

87 A

108 A

130 A

125 A

80 kVA

115 A

145 A

174 A

160 A

100 kVA

144 A

181 A

217 A

315 A

120 kVA

173 A

217 A

260 A

315 A

Standard UPS

UPS with backfeed

protection

Uin

380 to 443 V

380 to 443 V

Input voltage range permitted by the standard
according to the curve below

250 to 470 V

340 to 470 V

Fin

45 to 65 Hz

45 to 65 Hz

Uout

380 V

400 V

415 V

+ 3%

- 3%

Power supplied as a function of
input voltage

Permissible UPS overloads as a function of time

P/Pn

100%

70%

250V 340V 470V

U

I/In

2,2

2

1,8

1,6

1,4

1,2

1

10

4

10

1

0,1

t (s)

10

5

10

3

10

2

60

600