beautypg.com

Installation – APC GALAXY 5000 User Manual

Page 16

background image

34001813EN/AE

- Page 16

2. Installation

Required cable sizes for parallel UPS installations with an external bypass

Rated

power of

each UPS
unit

Number of

parallel

UPS units

Total rated

power of

the UPS

Bypass AC

input or

load line
current

Cable

size

(1)

in mm

2

The table opposite is an example for an

installation with up to four UPS units.

For installations with redundant units, take

into account only the number of units required

to supply the loads (e.g. in a three-unit

installation where one unit is redundant, only
two units count in determining the input and

load currents).

This table is valid for 400 V input and load

phase-to-phase voltages, at rated load with a

power factor of 0.8. For voltages of 380 or

415 V, multiply the current values by 1.05 or
0.96 respectively and, if necessary, modify

the cable sizes accordingly.

The cable sizes in this table concern the bold

sections in the diagram below.

(1) Cable sizes are determined for U1000
R02V type copper conductors (for aluminium

conductors, increase the size by 30%). Size

calculations also take into account a voltage
of 400 V and grouping of four cables.

20 kVA

2

3

4

40 kVA

60 kVA

80 kVA

58 A

87 A

116 A

16

35

50

30 kVA

2
3

4

60 kVA
90 kVA

120 kVA

80 A
129 A

172 A

25
50

70

40 kVA

2

3
4

80 kVA

120 kVA
160 kVA

116 A

174 A
232 A

35

70
120

60 kVA

2

3

4

120 kVA

180 kVA

240 kVA

174 A

261 A

348 A

70

150

185

80 kVA

2
3

4

160 kVA
240 kVA

320 kVA

232 A
348 A

464 A

120
185

2 x 120

100 kVA

2

3
4

200 kVA

300 kVA
400 kVA

288 A

432 A
576 A

150

2 x 95
2 x 150

120 kVA

2

3

4

240 kVA

360 kVA

480 kVA

348 A

522 A

696 A

185

2 x 150

2 x 185

Bypass AC

Normal AC

Bypass AC

GALAXY 5000

1

Normal AC

Bypass AC

GALAXY 5000

2

Normal AC

Bypass AC

GALAXY 5000

3

Load

External bypass