2. Installation

Frequency converter

To access the connection terminal blocks,
see section 1.2.

1 - The earthing conductors of each UPS

must be connected to the UPS earthing plate.
2 - Connect the neutral conductor of the

Normal AC source to the neutral terminal on

terminal block (15) of UPS1.
3 - Connect the three phases of the Normal

AC source to terminal block (16).

4 - Connect terminal block (16) in UPS1 to
terminal block (16) in UPS2 using the three

conductors of the Normal AC source.

5 - Connect the neutral cable on terminal
block (15) in UPS1 to terminal block (15) in

UPS2.

6 - Connect the four conductors supplying the
load to terminal block (14).

7 - Connect terminal block (14) in UPS1 to

terminal block (14) in UPS2 using the four
load conductors.

8 - Connect the neutral on terminal block (15)

with the neutral of the supplied loads on
terminal block (14).

9 - Tie the cables down to the frame.

10 - Put the cover back in place (see section
1.2).

Do not connect anything to the three

phases on the Bypass AC source terminal

block (15).

To normal
AC source

To load