20 6400

installation

guide

SW1 Switch 1:

Sets direction of the Primary actuator so that it cycles open upon initial power up and open command. If the actuator begins

to cycle close upon initial power up and open command, turn power off and change the setting on this switch.

SW1 Switch 2:

Sets direction of the Secondary actuator so that it cycles open upon initial power up and open command. If the actuator begins

to cycle close upon initial power up and open command, turn power off and change the setting on this switch

.

SW1 Switch 3:

Determines if the output of the loop detector (DoorKing loop detectors only) plugged into the EXIT port will be sent directly to

the microprocessor to open the gate, or if the output is directed to terminal 4 where it can then be connected to other input

terminals.

SW1 Switch 4:

Turns the auto close timer on or off. Maximum time that the close timer can be set for is 23 seconds.

SW1 Switch 5:

Sets the input to terminal 8 to act as a standard reverse input (OFF) or to act as a shadow input (ON). If shadow setting is

used, input to terminal 8 will only hold the gate in the full open position. Once the gate begins to close, the input will not reverse

the gate.

SW1 Switch 6:

Turns the overlap feature on or off. When turned ON, the Secondary actuator begins its cycle 1-2 seconds prior to the Primary

actuator, allowing the Primary gate to reach its full closed position 1-2 seconds before the Secondary gate. This feature is

useful when a magnetic lock is used to secure the gates.

SW1 Switch 7:

Sets up the circuit board for single or dual (Primary / Secondary) gate operation.

SW1 Switch 8:

Spare switch. Leave in the OFF position.

SW2 Switches 1-2:

Work in conjunction with each other and determine when the relay on the board will be activated. This relay can be used as a

switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the

gate is full open. This relay is not available for these uses if it is being used for the shadow loop function.

Switches 3-4:

Spare switches. Leave these in the OFF position.

settings / switch descriptions & functions

4

Switch

Function

Setting

Description

1

Direction
Primary

Set this switch so that the Primary actuator runs OPEN after
initial power up and activation.

2

Direction
Secondary

Set this switch so that the Secondary actuator runs OPEN
after initial power up and activation.

3

Exit Loop
Logic Output

OFF
ON (normal)

Output of loop detector in EXIT port is switched to terminal 4.
Output of loop detector in EXIT port feeds directly to processor.

4

Auto Close
Timer

OFF
ON

Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds.

5

Reverse
Shadow

OFF (normal)
ON

Terminal 8 is STANDARD reverse input.
Terminal 8 is SHADOW reverse input.

6

Overlap

OFF
ON

Both actuators start at same time.
Secondary actuator starts 1-2 seconds prior to the Primary actuator.

7

Single
Dual

OFF
ON

Switch is OFF for a single actuator.
Switch is ON for two actuators (Primary / Secondary).

8

Not Used

OFF

Leave in OFF position.

Switch

Function

Setting

Description

1 and 2

Relay
Operation

1-OFF 2-OFF

1-OFF 2-ON

1-ON 2-OFF

1-ON 2-ON

Relay activated only when gate is FULLY OPEN

Relay activated whenever gate is NOT CLOSED

Relay activated when gate is OPENING or OPEN

Relay activated when gate is OPENING or CLOSING

3

Mag-Lock
Solenoid

ON
OFF

1 Second Delay

4-5 Second Delay

4

Not Used

OFF

LEAVE in OFF position

SW2 (bottom switch)

SW1 (top switch)