beautypg.com

Controlled Products Systems Group 6400-080 User Manual

Page 15

background image

6400-065-E-05-07

6400 installation guide 15

electrical installation / main terminal wiring

3

TERMINAL DESCRIPTION

1. 24V COMMON
2. RADIO RELAY - SINGLE BUTTON ACTIVATION INPUT

• When gate is closed, input will open gate.
• When gate is open and auto close timer is turned on, input will re-set the hold timer.
• When gate is open and auto close timer is turned off, input will close gate.
• When gate is closing, input will reverse gate.

3. 24V DC RADIO POWER
4. SINGLE BUTTON ACTIVATION INPUT / EXIT LOOP LOGIC OUTPUT

• If SW 1, switch 3 is ON, this input is identical to Single Button Activation Input (Terminal 2).
• If SW 1, switch 3 is OFF, this terminal becomes the logic output of the EXIT loop detector.

5. 24V COMMON
6. OPEN INPUT
7. 24V COMMON
8. REVERSE INPUT / SHADOW INPUT

• When gate is closed, this input has no affect on the gate operator.
• When gate is open and auto close timer is turned ON, input will re-set and hold timer.
• When gate is open and auto close timer is turned OFF, input will prevent gate from closing.
• During CLOSING cycle of gate:

SW 1, Switch 5 OFF = Term 8 is Reversing Input.
SW 1, Switch 5 On = Term 8 is Shadow Input. Disabled During CLOSING CYCLE.

9. 24V COMMON
10. DRY RELAY CONTACT

• Operation of relay is dependent on setting of SW 2, switches 1 and 2. Relay contacts

can be set for Normally Open (NO) or Normally Closed (NC) operation. Contact
rating is 1 amp maximum at 24 Volts.

• Switch 1 OFF, Switch 2 OFF: Relay activates when gate is OPEN.
• Switch 1 OFF, Switch 2 ON: Relay activates when gate is OPEN, OPENING or CLOSING.
• Switch 1 ON, Switch 2 OFF: Relay activates when gate is OPEN or OPENING.
• Switch 1 ON, Switch 2 ON: Relay activates when gate is OPENING or CLOSING.

11. DRY RELAY CONTACT
12. SW2 - 3 ON MAG LOCK 1 SECOND DELAY AT START
13. SW2 - 3 OFF SOLENOID LOCK 4-5 SECOND DELAY AT START
14. Not Used
15. 12 VOLT BATTERY +
16. Not Used
17. ALARM RESET
18. 24V COMMON
19. 24 VAC INPUT
20. 24 VAC INPUT

*NOTE: DC power is not present on the board until the fi rst initial cycle.