beautypg.com

Controlled Products Systems Group 6002-080 User Manual

Page 27

background image

25

6002-065-M-6-08

Momentarily jumper terminal 1 to terminal 2. If the input LED does not come ON, check the terminal

strip or replace the circuit board. If LED does come ON, proceed to next steps.

Check the fuses.

Remove the circuit board. With two 14 AWG insulated jumper wires, momentarily jumper the battery

terminals to the motor terminals (1, 2) of the Primary actuator connector. The actuator should run.
Swap the two wires at the terminal strip. The actuator should run in the opposite direction. Repeat
these steps using the Secondary actuator connector.

If the actuator(s) run in both directions in the step above, replace the control board. If the

actuator(s) do not run, or run in only one direction, problem can be a bad actuator, wire connections
from the control board to the actuator(s) or a bad control board.

Check the reversing sensitivity.

Check the secondary safety devices.

Disconnect the gate from the gate operator and check that the gate swings freely without any

binding.

Replace the circuit board.

Actuator(s) will not
run. Power LED is
ON.

Gate closes and
opens continously.

Symptom

Possible Solution(s)

Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.

Check the secondary safety devices. Any activated will hold the gate open and indicates a problem

with the safety device.

Check the loop detectors. Any activated can hold the gate open and indicates a problem with the

loop detector or ground loop.

Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns

to normal operation.

If automatic close is desired, be sure SW 1, switch 4 is ON.

Gate opens a short
distance, then stops
and reverses.

Gate opens but
will not close.

Gate starts to close,
then reverses to
open.

Alarm sounds for 5
minutes and then
beeps once every 5
seconds. Operator
will not run.

Gate closes but
will not open.

Operator may be in a “soft shutdown.” Check input LEDs. If any are ON, momentarily disconnect,

then re-connect the wire going to the respective terminal. Operator should open.

Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back

ON. Activate a keying device. Operator should run in the open direction. If operator runs in the
close direction, turn power OFF and change direction switch SW-1, switches 1 and/or 2. Go to
above section if operator now opens but will not close.

Be sure that the respective LED on the control board lights when the keying device connected to the

respective terminal is activated. If LED does not light, momentarily place a jumper wire from
terminal 1 to the input terminal being checked. If LED lights and gate opens, problem is with the
keying device. If LED does not light, replace control board.

Check motor as described on previous page.

Disconnect the gate from the actuator and check that the gate operates freely without any binding.

Check the loop detector LED’s and input LED’s. Any that fl ash ON will cause the gate to reverse.

If a shadow loop is used, check for proper wiring. A mis-wired shadow loop detector will cause the

gate to reverse.

Replace the circuit board.

Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to

normal operation, see Hard Shutdown Section 3.5.

Check for any input or loop detector LED’s that are ON.

Check that the operator is running in the proper direction (see “gate closes but will not open” above).

Check the SELF TEST jumper, see page 20.