beautypg.com

Table e6 – CTI Products EXB-IP Ethernet System Extender User Manual

Page 50

background image

CTI Products, Inc.

EXB-IP User Guide

Appendix E - Troubleshooting

50

Table E6

Miscellaneous:

REASON

CORRECTIVE ACTION

Cannot communicate with

Control Neuron Processor
of local EXB when using
NODEUTIL.

1. In Bridge or Configured modes, router

neurons and network interface are not in
the same domain.

2. In Repeater mode, the network interface

may be defective.

1.

Verify that NODEUTIL can
communicate with other MCN
modules.

2a. Place the local router in Repeater mode

and verify that communications is
possible, or

b. Use NODEUTIL to change the

network interface Domain to match the
router neurons’ domains.

Cannot communicate with the

Control Neuron Processor
of local EXB.

1. In Bridge or Configured modes, the

Control Neuron, the router neurons, and
the network interface are not all in the
same domain.

2. In Repeater mode, the Control Neuron

and network interface are not in the same
domain.

1.

Place the router neurons for the local
EXB in Repeater mode.

2.

Change the network interface Domain
to match the Control Neuron domain.