3 - 36
Jog has the least operating priority. Jog ramps to the Jog Setpoint (CP-05), using the
Acceleration Time (CP-16). When Jog is terminated, the ML-Drive brings the drive
output to an immediate Zero. Unlike the other inputs, Jog is not latched and must be
sustained to remain active.
To activate Jog:
• Short the F–Stop and R–Stop inputs to common.
• Open the Run input.
• Short the Jog input to common. (Jog must be sustained to remain active).
R-STOP
F-STOP
RUN
JOG
COMMON
R-STOP
F-STOP
COMMON
JOG
RUN
Maintain Closed
6
7
8
9
10
11
J4