Figure 4-2 motor does not run flowchart – CONTREX ML-Drive User Manual
Page 115
![background image](/manuals/334452/115/background.png)
4 - 13
MP-50 =
0010(Master)
MP-50 =
0100(Follower)
MP-50 =
0001(Direct)
Yes
Motor Does Not Run
Problem
Corrected
Yes
Yes
No
No
No
No
Setpoint
is correct ?
No
Yes
MP-45 is
Correct ?
Enter Correct
Setpoint
No
Yes
MP-46 is
Correct ?
Enter Correct
Scaling
No
Yes
MP-47 is
Zero ?
Check
Wiring
CP-06
is correct ?
Yes
No
No
Yes
MP-53 =
1000 (F–Stop)
MP-53 =
0100 (R–Stop)
MP-53 =
0010 (Run)
MP-53 =
0001 (Jog)
No
Yes
Yes
No
No
No
No
No
J4, Pin 10 is
shorted
to common
J4, Pin 9 is
shorted
to common
Yes
Short J4,
Pin 10
to common
Problem
Corrected
No
Consult Tech
Support
Yes
Yes
No
Yes
CP-05
is correct ?
Yes
No
Enter Correct
Jog Setpoint
Short J4,
Pin 9
to common
No
No
Consult Tech
Support
1-800-342-4411
Figure 4-2 Motor Does Not Run Flowchart