2 meaning of the diagnostic values, Meaning of the diagnostic values – Cashco Siemens PS2 I/P User Manual

Page 91

background image

Operation

91

SIPART PS2 Manual

A5E00074631-01

No.

Rest

poss.

Unit

Displayable

values

Meaning

Abbrevia-

tion

28

T7

Number of operating hours in Temperature range 7

0 to 4.29E9

Hours

29

T8

Number of operating hours in Temperature range 8

0 to 4.29E9

Hours

30

T9

Number of operating hours in Temperature range 9

0 to 4.29E9

Hours

31

VENT1

Number of cycles pre--controlvalve 1

0 to 4.29E9

--

32

VENT2

Number of cycles pre--controlvalve 2

0 to 4.29E9

--

33

STORE

Store current values as ”last maintenance”

(press increment key for 5 s) (Store)

--

--

Table 3-1

Overview diagnostic values

4.5.2 Meaning of the diagnostic values

Number of strokes
The actuator movements during operation are totaled and can be read

here as number of strokes. Unit: 100% stokes The value is written

every hour in a non--volatile memory. It can be reset to zero with the
increment key

.

Number of direction changes
Every change in direction leaving the dead zone is noted in the

controller and added to the number of changes of direction.
The value is written every hour in a non--volatile memory. It can be
reset to zero with the increment key

.

Fault counter
Every fault is noted in the controller and added to the number of fault
messages. The counter can be reset to zero with the increment key

.

Alarm counter 1

and

Alarm counter 2
Responses of alarm 1 and alarm 2 are counted with these two

counters. The prerequisite is the activation of the alarms with the

parameter “44.AFCT”. The counters can be reset to zero with the
increment key

.

Operating hours
The operating hours counter is updated every hour as soon as the

positioner has been supplied with electrical power.

1 STRKS

2 CHDIR

3 CNT

4 A1CNT

5 A2CNT

6 HOURS