Preparing for Operation

61

SIPART PS2 Manual

A5E00074631-01

3.6.3

Manual initialization of linear actuator

The positioner can be initialized with this function without the actuator

being driven hard against the limit stop. The start and end positions of

the displacement path are set manually. The other initialization steps

(optimization of the control parameters) run automatically as in automa-

tic initialization.

1.

Make preparations as described in chapter 3.6.1, page 58 for

linear actuator. In particular, make sure by manuallydriving the whole

displacement path that the displayed potentiometer setting moves

in the permissible range between P5.0 and P95.0.

Press the operation mode key

for longer than 5 s. This brings

you to the Configuration operating mode.

Display:

3.

Switch to the second parameter by pressing the operation mode
key

briefly. One of the following displays appears:

or

.

NOTE
It is vital that this value corresponds to the setting of the transmission

ratio selector (33_ or 90°).

4.

Switch on to the following display

with the operation mode key:

You only need to set this parameter if you want to have the total

stroke in mm displayed at the end of the initialization phase. To do

this, select the same value in the display to which you have set

the carrier pin to the scale on the lever or the next highest position

in intermediate positions.

Manual initializa-

tion procedure in

linear actuator