English, Version with analogue signal, 22 installation – Burkert Type 3005 User Manual
Page 22: Fig. 21: circuit diagram procedure, Type 3005

22
Installation
9.2.3. Version with analogue signal
The power supply voltage of the actuator is 15-30 V AC
(12-48 V DC) or 100-240 V AC ( 100-350 V DC).
Always observe the specifications on the type label!
T/E
FC2
FC1
FCF
FC0
4-6
5
7
=
C
B
D
D
A
C
2
17
18
18
17
N
-
Ph
+
N
-
Ph
+
3
1
16
15
14
13
+
-
-
+
Feedback
Input
Power supply
24 V DC
Feedback
Power supply
100 - 240 V AC
(120 - 350 V DC)
or
15-30 V AC
(12-48 V DC)
0
-
20
mA
/
4
-
20
mA
/
0
-
10
V
Motor
Fig. 21: Circuit diagram
procedure:
→
Loosen left cable gland 15 and feed through the cable to be
connected.
→
Connect cable according to the circuit diagram (see “Fig. 21”) to
the terminal strip Pos. 14 of the power supply card.
connecting additional feedback
The limit switches for the feedback are suitable for a
maximum voltage of 250 V AC/DC - 5 A.
The rotary actuator features two limit switch contacts which are sup-
plied by the factory in an open position. These can be used for the
feedback of the rotary actuator.
The limit switch contacts are actuated via two cams no. 13.
• The white cam is used to record the opening process (FC1).
• The black cam is used to record the closing process (FC2).
procedure:
→
Connect cable to the terminal strip 12 according to the
schematic.
english
Type 3005