Installation

Connect cable according to the required control type to the terminal
strip Pos. B of the power supply circuit board.

operating principle for open / closed mode:
• Switch open = actuator closes
• Switch closed = actuator opens
connecting feedback

The limit switches for the feedback are suitable for a
maximum voltage of 250 V AC/DC - 5 A.

The rotary actuator features two additional limit switch contacts which
are supplied by the factory in an open position. These can be used for
the feedback of the rotary actuator.

2

3

1

FC2

FC1

FCF

FC0

4-6

5

7

=

C

C

A

B

D

D

T/E

Feedback

Power supply and control

Motor

Fig. 20: Internal wiring of actuator

The limit switch contacts are actuated via two cams no. 13 (see
Fig. 1 and Fig. 2).
• The white cam is used to record the opening process (FC1).
• The black cam is used to record the closing process (FC2).
procedure:

Connect cable to the terminal strip 12 (see “Fig. 1” and “Fig. 2”)
according to the schematic (see “Fig. 20”).

english

Type 3005