beautypg.com

Burkert Type 3005 User Manual

Page 15

background image

15

TechnicalData

7.5.3. electrical Data

Connections:

2 threaded connections ISO M20

Limit switches:

2 adjustable limit switches for the motor
2 potential-free limit switches (for position
feedback)

Output: max.

250 V AC / 5 A

electrical data for standard version without analogue signal and
position controller version with 4 – 20 ma, 0 – 20 ma or 0 – 10
V analogue input signal

torque

[nm]

90° actu-

ating time

[s]

power

input

[W]

Voltage /

frequency

[V / hz]

25

7

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

45

15

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

75

20

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

torque

[nm]

90° actu-

ating time

[s]

power

input

[W]

Voltage /

frequency

[V / hz]

100

15

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

150

30

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

300

60

45

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

600

38

250

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

1000

38

250

100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC

1)

)

We recommend an actuator designed with 1.5 times the
maximum torque of the fitting (with 2 times the maximum
torque for variable speed actuators).

1)

The operating voltage must not drop below 11.5 V

english

Type 3005