TechnicalData
7.5.3. electrical Data
Connections:
2 threaded connections ISO M20
Limit switches:
2 adjustable limit switches for the motor
2 potential-free limit switches (for position
feedback)
Output: max.
250 V AC / 5 A
electrical data for standard version without analogue signal and
position controller version with 4 – 20 ma, 0 – 20 ma or 0 – 10
V analogue input signal
torque
[nm]
90° actu-
ating time
[s]
power
input
[W]
Voltage /
frequency
[V / hz]
25
7
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
45
15
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
75
20
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
torque
[nm]
90° actu-
ating time
[s]
power
input
[W]
Voltage /
frequency
[V / hz]
100
15
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
150
30
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
300
60
45
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
600
38
250
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
1000
38
250
100-240 / 50/60
(100-350 DC)
15-30 AC (12-48 DC
1)
)
We recommend an actuator designed with 1.5 times the
maximum torque of the fitting (with 2 times the maximum
torque for variable speed actuators).
1)
The operating voltage must not drop below 11.5 V
english
Type 3005