Wiring instructions for a wall-mounted version – Burkert Type 8025 User Manual
Page 40
40
Wiring
Type 8025 / 8035
→
Insert the cable clips: see "Fig. 25".
The wiring of the current output and the pulse output of the panel or wall-mounted transmitter, 12-36 V DC, without relays, are
the same as for a compact flowmeter, 12-36 V DC, with relays, with cable glands.
→
Wire the current output according to "Fig. 31" of chap. "8.4.4".
→
Wire the pulse output according to "Fig. 32" of chap. "8.4.4".
8.7.
Wiring the 8025, wall-mounted version, 115/230 V Ac, with or
without relays
8.7.1. Wiring instructions for a wall-mounted version
Seal the unused cable gland using the supplied stopper gasket to make sure the device is tight.
→
Unscrew the nut of the cable gland.
→
Remove the transparent disc inside the cable gland.
→
Insert the stopper gasket
→
Screw the nut back.
→
Connect the flow sensor to the remote transmitter according to chap. "8.5".
→
Configure the selectors on the electronic board: see chap. "8.3".
→
Loosen the nuts of the cable glands.
→
Insert each cable through a nut then through the cable gland, using the cable glands as shown in "Fig. 43".
Flow sensor cable
Cables of the outputs
Power supply cable,
12-36 V DC or
115/230 V AC
Fig. 43: Using the cable glands
→
Remove the two terminal blocks (marked 4 and 6 in "Fig. 44" chap. "8.7.2" and "Fig. 48" chap. "8.7.3") from the housing.
→
For the versions with relays, insert the cable clips: see "Fig. 25".
→
Depending on the version (with or without relays), wire the device according to chap. "8.7.2" or "8.7.3".
→
Insert the two terminal blocks (marked 4 and 6 in "Fig. 44" chap. "8.7.2" and "Fig. 48" chap. "8.7.3") into their original
position.
→
Letting the housing stay completely open, secure the power supply cable, the flow sensor connection cable and,
depending on the version, the relay connection cables, with the cable clips.
→
Tighten the cable glands making sure the cable in the housing is long enough to allow complete opening of the housing.
→
Close the cover.
→
Tighten the 4 screws.
→
Put the blanking strips on the housing.
English