Electrical data – Burkert Type 8025 User Manual
Page 19

19
Technicaldata
Type 8025 / 8035
6.5.
electrical data
12-36 V DC power supply
• filtered and regulated
• SELV circuit (safety extra low voltage), with a safe energy
level
• oscillation rate: ±10 %
Power source (not supplied)
• limited power source according to paragraph 9.3 of
EN 61010-1 standard
• or class 2 source according to UL 1310/1585 and
EN 60950-1 standards
115/230 V AC power supply
• frequency
• supplied voltage
• current
• integrated protection
• power
• 50/60 Hz
• 27 V DC, regulated
• max. 250 mA
• 250 mA time-delay fuse
• Compact version: 6 VA
• Wall-mounted version 3 VA
Current consumption (without the consumption of the
4-20 mA output)
• 12-36 V DC version with relays
• 12-36 V DC version without relays
• 115/230 V AC compact version
• 115/230 V AC wall-mounted version
• 70 mA max. (at 12 V DC)
• 25 mA max. (at 12 V DC)
• 125 mA max. (at 27 V DC)
• 250 mA max. (at 27 V DC)
Pulse output
• type
• function
• frequency (f)
• electrical data
• duty cycle
• protection
polarized, potential-free
• NPN/PNP (wiring dependant)
• pulse output, adjustable pulse value
• 2,5-400 Hz
• 5-36 V DC, 100 mA max., voltage drop 2,5 V DC at
100 mA
• 0,5
• galvanically insulated, and protected against overvoltages,
polarity reversals and short-circuits
Relay outputs
• operating
• electrical data of the load (non UL recognized devices)
• electrical data of the load (UL recognized devices)
• hysteresis, adjustable thresholds, normally open
• 230 V AC / 3 A
• 30 V AC max. and 42 V peak or 60 V DC max.
Current output
• response time (10% to 90%)
• max. loop impedance, 12-36 V DC version
• max. loop impedance, 115/230 V AC version
• wiring, version without relays
• wiring, version with relays
4-20 mA, sinking or sourcing mode (wiring dependant)
• 5,75 s (default)
• 900 W at 30 V DC, 600 W at 24 V DC, 50 W at 12 V DC
• 800 W
• 2-wire
• 3-wire
Protection against polarity reversals
yes
English