English, 32 1 a – Burkert Type 8025 User Manual
Page 39
39
Wiring
Type 8025 / 8035
Supply
12..36Vdc
FLOW SENSOR
COIL
NPN
L+
L-
PE
P-
P+
NC
L+
L-
PE
P-
P+
Iout
PULSE
OUTPUT
Without
With
Relays
NPN SENSOR
1 PULSE INPUT
2 -
3 +
4 NC
SUPPLY
1
2
3
4 PE
REL1
REL2
COIL SENSOR
1
2
3 NC
4 NC
3
2
1
A
PE
Switch A : see chap. "8.3.1"
terminal block 1
NC: not connected
L+: positive power supply
L-: negative power supply
PE: wiring of the PE between the main board and the
protection board
P-: negative pulse output
P+: positive pulse output
terminal block 2 pe
Wiring of the cable shields
connector 3: connection of the flow sensor see chap.
"8.5"
Fig. 41: Terminal assignment of a panel-mounted or wall-mounted version, 12-36 V DC, without relays
The wiring of the current output and the wiring of the pulse output of the panel or wall-mounted transmitter, 12-36 V DC,
without relays, are the same as for a compact flowmeter, 12-36 V DC, without relays, with cable glands.
→
Wire the current output according to "Fig. 28" of chap. "8.4.3".
→
Wire the pulse output according to "Fig. 29" of chap. "8.4.3".
8.6.2. Wiring the 8025, remote version, 12-36 V Dc, with relays
→
For a wall-mounted version, obey the wiring instructions of chap. "8.7.1".
→
Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").
→
Connect the flow sensor to the transmitter according to chap. "8.5".
Supply
12..36Vdc
FLOW SENSOR
COIL
NPN
L+
L-
PE
P-
P+
NC
L+
L-
PE
P-
P+
Iout
PULSE
OUTPUT
Without
With
Relays
NPN SENSOR
1 PULSE INPUT
2 -
3 +
4 NC
SUPPLY
1
2
3
4 PE
REL1
REL2
COIL SENSOR
1
2
3 NC
4 NC
4
6
3
5
A
2
1
B
PE
Switch A : see chap. "8.3.1"
Switch B : see chap. "8.3.2"
terminal block 1
Iout: 4-20 mA output
L+: positive power supply
L-: negative power supply
PE: wiring of the PE between the main board and the protection
board
P-: negative pulse output
P+: positive pulse output
terminal block 2 pe
Wiring of the cable shields
terminal block 3: wiring of relay 1, see chap. "8.4.2"
terminal block 4: wiring of relay 2, see chap. "8.4.2"
connector 5: connection of the flow sensor: see chap. "8.5"
Jumper wire 6: jumper wire to be removed if the 4-20 mA
output is connected
Fig. 42: Terminal assignment of a panel-mounted or wall-mounted version, 12-36 V DC, with relays
English