Specifications of the connected flow sensor, Electrical connection – Burkert Type 8025 User Manual
Page 20
20
Technicaldata
Type 8025 / 8035
6.6.
specifications of the connected flow sensor
Sensor input
• signal frequency
• pulse signal (Hall)
• sinus signal (coil)
• 2,5 to 400 Hz
• NPN, open collector
• typical sensitivity of 35 mV peak-peak, at 252 Hz
Sensor output
• power supply
• 10-34 V DC (V+ minus 2 V DC), 1 mA max.
6.7.
electrical connection
Version
connection features
With male fixed
connector
Female connector (type 2508 supplied)
For the female connector type 2508 with order code 438811 and the female connector type 2509
(not supplied) with order code 162673, use a shielded cable.
• external diameter of the cable: 5 to 8 mm
• cross section of the wires: 0.2 to 1.5 mm
2
• max. length of the power supply, current output and pulse output connection cables: 50 m
With terminal strip,
with or without cable
glands
Shielded cable (not supplied):
• external diameter of the cable: 6 to 12 mm (4 to 6 mm when using a multiway seal)
• cross section of the wires: 0.2 to 1.5 mm
2
All
Cross section of the local earthing wire: 0.75 mm
2
English