Installation of the 8025 on the s020 fitting – Burkert Type 8025 User Manual
Page 24

24
Installation
Type 8025 / 8035
7.2.2. installation of the 8025 on the s020 fitting
2
1
3
4
5
6
→
Install the S020 fitting onto the pipe obeying the instructions in chap. “7.2.1”.
→
Check that there is a seal on the fitting and that it is not damaged. Replace the seal if
necessary.
→
Insert the nut 3 on the fitting 5.
→
Insert the snap ring 2 into the groove 4.
→
Check that the seal 6 is correctly inserted on the flow sensor.
→
Insert the device 1 into the fitting.
If the mounting is correctly done the device cannot be turned around anymore.
→
Hand lock the assembly with nut 3.
Fig. 11: Installation of the 8025 on the S020 fitting
7.2.3. installation of the se35 electronic module onto the s030 sensor-fitting
1
2
3
→
Respect the installation instructions contained in the operating instructions of
the fitting used.
→
Insert the electronic module 2 into the S030 sensor-fitting.
→
Fix with a 30° rotation.
→
Tighten the side screw 3 to lock the electronic module to the sensor-fitting.
Fig. 12: Installation of the SE35 onto the S030 sensor-fitting
English