Burkert Type 8709 User Manual
Page 32

32
Installation and Start-up
pin assignment lfc type 8718 and lfM type 8708
lfc type 8718:
plug suB-d 15-pole
pin
configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
Relay – Normally closed contact
2
Relay – Normally open contact
3
Relay – Centre contact
4
GND for 24 V supply and binary inputs
5
24 V – supply +
6
8 V output (for internal use only)
7
2)
Set-point value input GND
8
2)
Set-point value input +
9
2)
Actual value output GND
10
2)
Actual value output +
11
DGND (for RS232)
12
Binary input 1
13
Binary input 2
14
RS232 R x D (without driver)
15
RS232 T x D (without driver)
lfM type 8708:
plug suB-d 15-pole
pin
configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
Relay – Normally closed contact
2
Relay – Normally open contact
3
Relay – Centre contact
4
GND for 24 V supply and binary inputs
5
24 V – supply +
6
8 V output (for internal use only)
7
not used
8
not used
9
2)
Actual value output GND
10
2)
Actual value output +
11
DGND (for RS232)
12
Binary input 1
13
Binary input 2
14
RS232 R x D (without driver)
15
RS232 T x D (without driver)
Pin assignment LFC Type 8718 and LFM Type 8708
Table 2:
2)
In the field bus version the connections 7 – 10 are not used.
english
Type 8718, 8719 / 8708, 8709