Installation and Start-up
7.5.1.
setting the bus address on devices without rotary switch
for setting the address
The bus address of the devices can be set either via the Bürkert configuration tool “Mass Flow Communicator” in
"Views" → PROFIBUS / DeviceNet / CANopen or directly via the bus master.
When an address has been changed, it must be re-initialised on the slave and on the master. In doing so, it is
necessary, depending on the bus, to send a corresponding telegram.
Recommendation:
To ensure a trouble-free setting, the device should be reset.
(Disconnect the device from the power supply).
setting the bus address on devices with rotary switch for
7.5.2.
setting the address (Types 8718 / 8708)
When the device is switched on, the address set with the rotary switches is accepted as a slave address.
Valid addresses are: • PROFIBUS
0 – 126
• DeviceNet
0 – 63
• CANopen
1 – 127
If the address was set outside the permitted range, the address setting has the validity as described in Chapter
7.5.1. .
lsB
Unit position (x 1)
Unit position Digit times 1
0 – 9
0 – 9
MsB
Tens position
(x 10)
Tens position Digit times 10
0 – 9
0 – 90
A
100
B
110
C
120
D
130
E
140
F
150
The address is composed of LSB + MSB
Example:
address
MsB setting
lsB setting
1
0
1
63
6
3
100
A
0
127
C
7
Setting the bus address on devices with rotary switch (Types 8718 / 8708)
Fig. 10:
If an address setting is required using the available rotary switches via the bus master, this can be
implemented by setting an address outside the valid range.
A change to the bus address via the rotary switches does not become effective until the device is
restarted.
english