Installation

8.5.1.

pneumatic connections - feed



Exhaust air

Pressure supply connection

X channel:
Standard version:
Deaeration of the control valves
Control assist air version:
P connection for control valves

(R/S) 3/5

(P) 1

Figure 31:

Pneumatic connections

Procedure

Depending on the version, insert (D10) or screw (G1/4, NPT 1/4) the connections to the corresponding working
connections.

NoTE!

For the plug-in connections the hose pipes must meet the following requirements:

• Minimum hardness of 40 Shore D (in accordance with DIN 53505 or ISO 868);

• Outer diameter in accordance with DIN 73378 (max. permitted deviation ± 0.1 mm of the nominal dimension);

• Burr-free, cut off at right angles and undamaged on the outer diameter;

• The hose pipes must be pressed all the way into the plug-in connections.

8.5.2.

removing the plug-in connections

To detach the pipes, press in the thrust ring and pull out the hose pipe.