Electronic base module me03 / 4-fold monostable – Burkert Type 8644 User Manual
Page 44
44
Structureandfunctionofthemodules
7.3.7.
electronic base module me03 / 4-fold monostable
Structure
An electrical base module consists of a distributor module (backplane bus) and a function module. Both modules
are contacted via a 14-pole board-to-board plug. The bus signals on the distributor module are protected from
interference by a shield support.
Combination options with valve types
Base module type
add-on
dimension
Valve locations
Valve type
Operating principle
ME03 4-fold monostable
16.5 mm
4
6526
3/2-way
6527
5/2-way
The function module can be disconnected and connected during operation the same as the electronic modules of
the ET200S. If several modules are replaced, the modules must be disconnected and reconnected in succession
(5-23 ET200S EWA4NEB 780602401-06). To ensure the switching process, 24 V is applied briefly to the valve
when connected. The power on the valve is reduced to one quarter after approx. 400 ms.

Function display of the LEDs
No function
Yellow LED “on”
valve coil powered
Pin assignment of valve plug
1
Not used
2
Valve +
3
Valve -
4
Not used
1
2
3
4
Figure 22:
Electronic base module ME03 / 4-fold monostable
english
Type 8644