Configuring the network

Description of the block parameters of the transducer

9.2.2.5.

Suitable for solenoid valve application;

Two proximity switches for each solenoid outlet;

The input signals indicate the ON/OFF status of the valve.

parameter

Description

ValVE_man

Name of the valve manufacturer

aCtuator_man

Name of the actuator manufacturer

ValVE_sEr_num

Serial number of the valve belonging to the device

aCtuator_sEr_num Serial number of the actuator belonging to the device
ValVE_iD

Identification of the valve (valve type)

aCtuator_iD

Identification of the actuator (actuator type)

aCtuator_aCtion

Safety position if actuator or valve has power failure:

0 not initialized
1 open
2 closed

traVEl_Count

Number of cycles from “open” to “closed” and from “closed” to “open”. The number
range of the TRAVEL_COUNT exceeds the storage capability of the EEPROM

traVEl_Count_lim

Limit of the parameter TRAVEL_COUNT; if 0, TRAVEL_COUNT_LIM is not pro-
cessed. If the LIMIT values are exceeded, the corresponding bit in the parameter
CHECK_BACK is set.

traVEl_timE_ClosE_
opEn

Set-point value for the time in seconds between the change of status from CLOSED
to OPEN; if 0, the time is not processed. If the time is exceeded, the corresponding
bit in the parameter CHECK_BACK is set. Times less than 0.5 seconds cannot be
monitored.

traVEl_timE_opEn_
ClosE

Set-point value for the time in seconds between the change of status from OPEN to
CLOSED; if 0, the time is not processed. If the time is exceeded, the corresponding
bit in the parameter CHECK_BACK is set. Times less than 0.5 seconds cannot be
monitored.

traVEl_timE_ClosE_
opEn_tol

Maximum time difference between TRAVEL_TIME_CLOSE_OPEN and the current
switching time

traVEl_timE_opEn_
ClosE_tol

Maximum time difference between TRAVEL_TIME_OPEN_CLOSE and the current
switching time

sElf_CaliB_CmD

Device-specific calibration

- - - - - - x y

y = 0

de-energized active

y = 1

energized active

x = 0

Sensor 1 displays “Valve open”

x = 1

Sensor 1 displays “Valve closed”

sElf_CaliB_status

Result or status of the device-specific calibration (depending on manufacturer)

0 Standard setting