Configuring the network
Description of the block parameters of the transducer
9.2.2.5.
Suitable for solenoid valve application;
•
Two proximity switches for each solenoid outlet;
•
The input signals indicate the ON/OFF status of the valve.
•
parameter
Description
ValVE_man
Name of the valve manufacturer
aCtuator_man
Name of the actuator manufacturer
ValVE_sEr_num
Serial number of the valve belonging to the device
aCtuator_sEr_num Serial number of the actuator belonging to the device
ValVE_iD
Identification of the valve (valve type)
aCtuator_iD
Identification of the actuator (actuator type)
aCtuator_aCtion
Safety position if actuator or valve has power failure:
0 not initialized
1 open
2 closed
traVEl_Count
Number of cycles from “open” to “closed” and from “closed” to “open”. The number
range of the TRAVEL_COUNT exceeds the storage capability of the EEPROM
traVEl_Count_lim
Limit of the parameter TRAVEL_COUNT; if 0, TRAVEL_COUNT_LIM is not pro-
cessed. If the LIMIT values are exceeded, the corresponding bit in the parameter
CHECK_BACK is set.
traVEl_timE_ClosE_
opEn
Set-point value for the time in seconds between the change of status from CLOSED
to OPEN; if 0, the time is not processed. If the time is exceeded, the corresponding
bit in the parameter CHECK_BACK is set. Times less than 0.5 seconds cannot be
monitored.
traVEl_timE_opEn_
ClosE
Set-point value for the time in seconds between the change of status from OPEN to
CLOSED; if 0, the time is not processed. If the time is exceeded, the corresponding
bit in the parameter CHECK_BACK is set. Times less than 0.5 seconds cannot be
monitored.
traVEl_timE_ClosE_
opEn_tol
Maximum time difference between TRAVEL_TIME_CLOSE_OPEN and the current
switching time
traVEl_timE_opEn_
ClosE_tol
Maximum time difference between TRAVEL_TIME_OPEN_CLOSE and the current
switching time
sElf_CaliB_CmD
Device-specific calibration
- - - - - - x y
y = 0
de-energized active
y = 1
energized active
x = 0
Sensor 1 displays “Valve open”
x = 1
Sensor 1 displays “Valve closed”
sElf_CaliB_status
Result or status of the device-specific calibration (depending on manufacturer)
0 Standard setting