beautypg.com

Connection terminals for cable connections, Terminal allocation plan – Burkert Type 8631 User Manual

Page 21

background image

8631 - 19

C

OMMISSIONING

english

230 V - version with mechanical limit switches

2

1

N

L1

Electrical installation of the TOP Control on/off with EEx-i
approval

The electrical connection of the TOP Control on/off with EEx-i approval is made using the connection
terminals.

Connection terminals for cable connections

Open the housing.

Connect the wire according to the Terminal Allocation Plan.

Plug for initiator /
proximity sensor 1

Plug for initiator /
proximity sensor 2

Terminal Allocation Plan

NC1 (max. 5 A)

NO1 (max. 5 A)

NC2 (max. 5 A)

NO2 (max. 5 A)

L1

9

7

8

5

6

S1

S2

4

3

Output common pole

N

Terminal

no.

Allocation

External connection

1

Valve actuation N

2

Valve actuation L1

3

Limit switch supply

4

Output common pole

5

Output limit switch 2 (NC)

6

Output limit switch 2 (NO)

7

Output limit switch 1 (NC)

8

Output limit switch 1 (NO)

9

Limit switch supply