English electrical data without bus control, Electrical data with bus control (as interface), Electrical data with bus control (devicenet) – Burkert Type 8631 User Manual
Page 15

8631 - 13
T
ECHNICAL
D
ATA
english
Electrical data without bus control
Connections
2 x M16 cable bushings with screw terminals for
cable cross-sections 0,14 ... 1,5 mm²
Voltage supply
24 V DC ± 10 % residual ripple 10%
ATTENTION: Do not use industrial DC!
110 V AC / 230 V AC
Power consumption
< 2 W
Electrical data with bus control (AS interface)
Connections
M12 circular plug connectors or
M20 cable bushings with screw terminals for
cable cross-sections 0,14 ... 1,5 mm² (seal for AS interface flat
cable is enclosed)
Voltage supply
29.5 ... 31.6 V DC (to specification)
Max. current consumption
120 mA
in normal operation
≤
80 mA
after current reduction
≤
50 mA
Outputs
Max. switching capacity
1 W via AS interface
Watchdog function
integral
Inputs
Sensor supply
via AS interface
Sensor supply voltage
24 V ± 10 %
Current loading capacity
max. 60 mA, short-circuit proof
Switching level of 1 signal
≥
10 V
Input current limited to
6.5 mA
Input current for 0 signal
≤
1.5 mA
Electrical data with bus control (DeviceNet)
Connection
M12 - Micro Style circular plug 5-pole
Voltage supply
11 ... 24 V
Max. current consumption
125 mA
Outputs
Pick-up current
120 mA
Holding current
80 mA
Inputs
"0"
0 ... 1.5 V
"1"
≥
8 V