beautypg.com

English electrical data without bus control, Electrical data with bus control (as interface), Electrical data with bus control (devicenet) – Burkert Type 8631 User Manual

Page 15

background image

8631 - 13

T

ECHNICAL

D

ATA

english

Electrical data without bus control

Connections

2 x M16 cable bushings with screw terminals for
cable cross-sections 0,14 ... 1,5 mm²

Voltage supply

24 V DC ± 10 % residual ripple 10%

ATTENTION: Do not use industrial DC!

110 V AC / 230 V AC

Power consumption

< 2 W

Electrical data with bus control (AS interface)

Connections

M12 circular plug connectors or

M20 cable bushings with screw terminals for
cable cross-sections 0,14 ... 1,5 mm² (seal for AS interface flat
cable is enclosed)

Voltage supply

29.5 ... 31.6 V DC (to specification)

Max. current consumption

120 mA

in normal operation

80 mA

after current reduction

50 mA

Outputs

Max. switching capacity

1 W via AS interface

Watchdog function

integral

Inputs

Sensor supply

via AS interface

Sensor supply voltage

24 V ± 10 %

Current loading capacity

max. 60 mA, short-circuit proof

Switching level of 1 signal

10 V

Input current limited to

6.5 mA

Input current for 0 signal

1.5 mA

Electrical data with bus control (DeviceNet)

Connection

M12 - Micro Style circular plug 5-pole

Voltage supply

11 ... 24 V

Max. current consumption

125 mA

Outputs

Pick-up current

120 mA

Holding current

80 mA

Inputs

"0"

0 ... 1.5 V

"1"

8 V