beautypg.com

English operating conditions, Conformity, Mechanical data – Burkert Type 8631 User Manual

Page 14: Pneumatic data

background image

12 - 8631

T

ECHNICAL

D

ATA

english

Operating conditions

Operating temperature

-10 ... + 50 °C

Protection type

IP 65 to EN 60529

TOP Control on/off with EEx-i approval:

Type of "e" protection

II 2 G EEx ia IIC T6

Conformity

CE - symbol conformity wrt. EMC Guideline 89/336/EEC

(only with correctly connected cable or plugs and sockets)

TOP Control on/off with EEx-i approval:

PTB approval

according to DIN EN 50014 and 50020

Mechanical data

Dimensions

see data sheet

Housing material

outer: PPE / PA, PSU; inner: PA 6

Sealing material

outer: EPDM; inner: NBR

Pneumatic data

Control medium

quality classes to DIN ISO 8573-1

Dust content

class 5:

max. particle size 40 µm, max. particle density

10 mg/m

3

Water content

class 3:

max. pressure dew point - 20°C or min. 10

degrees below the lowest operating temperature

Oil content

class 5:

max. 25 mg/m³

Temperature range of

compressed air

-10 ... +50°C

Pressure range

3 ... 7 bar

Variation of supply pressure

-

Air flow rate of control valve

100 l

N

/ min (for pressurizing and exhausting)

(Q

Nn

-value to definition for pressure drop from 7 to 6 bar abs.)

Internal air consumption as

dimensioned

0.0 l

N

/min

Connections

1/4’’ internal thread G / NPT / RC

ATTENTION!

The TOP Control on/off is not suitable for outdoor use!

TOP Control on/off with EEx-i approval:

Note the Manufacturer's Declaration for proximity switches.