C-4-3-2 Batch and Blend Control Commands

These commands are provided to conduct output port control operations
that require starting and stopping.

Batch Command

This command is used to start a new batch quantity process, or stop a
batch process that may currently be in processing.

Bulk Batching

Bulk batching starts all qualified batch processes for all qualified channel
ports at the same time.

Qualified channel output ports [Control Function] must be programmed to
[Batch] and [Batch Quantity] set greater than zero, with [Link] to the
channel input port programmed to accumulate quantity.

HOST SEND

AZ F*

start all channel batches

AZ F

stop all channel batches

RESPONSE(S)

AZ,[yyyyy.xx],5,FOK,DA,

batch started and in process

AZ,[yyyyy.xx],5,FDONE,4E,

batch(s) completed

AZ,[yyyyy.xx],5,FERROR,5D,

command error