Section C Serial Communications Protocol

Installation and Operation Manual

X-SE-0254-eng

Part Number: 541B129AAG

September, 2010

C-5-4 Channel Output Port Values

Port Type is the output signal type and is the first serial character received
when programming a new

Type. An optional second or third

character may be received after Port Type with a range of 0-99 and has no
operational effect. These characters represent the port number of the
linked input and are always returned when Port Type is serially
interrogated.

Index

Value Title

Value

Range

Notes

_____

____________

_____

_________________

_______________

0

Port Type

1 or 2 ascii chars

with second or third

chars range 0-99 not

affecting proper

operation

0 Off

1 ascii char min

1 0-20mA

2 4-20mA

3 0-10V

4 2-10V

5 0-5V

6 1-5V

Link Input Port

0-99

1 or 2 ascii char

optional

Rate (Manual) output set-point

1

SP Rate

xxxxxx

0 to ±999.999

1-7 ascii char var

dp

Select output control service

2

SP Function

1 Rate

1 ascii char

2 Batch

3 Blend

Analog De-Interpolate representing the engineering units of the greatest signal allowed

9

SP Full Scale

xxxxxx

0 to ±999.999

1-7 ascii char var

dp

Valve Override valve state selection

29

SP VOR

0-2

1 ascii char

0 Normal

tri-state

1 Closed

vo < -4V

2 Open

vo > +8V

Batch Delivery Set-Point

44

SP Batch

xxxxxx

0 to ±999.999

1-7 ascii char var

dp

Blend Mixing Set-Point

45

SP Blend

xxxxxx

0 to ±999.999

1-7 ascii char var

dp (automatic %

units)

Set-Point Programming Source

46

SP Source

0-1

1 ascii char

0 Keypad

1 Serial

keypad prohibit