beautypg.com

Parallel/series connection, Connection and setup, Connection – B&K Precision 9116 - Manual User Manual

Page 44

background image

31

5.

When finished, press

. The screen will return to the CONFIG menu.

6.

Press

several times to exit the menu.

Parallel/Series Connection

More than one unit of the same model can be connected in a parallel or series configuration.

Table 3.2 below shows the total number of units that can be connected in each configuration.

The power supplies can be set up in master/slave mode so that the master unit can control all

other power supplies in the parallel or series connection.

Note: Master/slave configurations and RS-485 connections must be properly set up prior

to controlling the power supplies in parallel/series connection. However, RS-485

does not have to be set as the Communication interface for master/slave operation

to function.

Table 3.2 – Series/Parallel Configuration Table

Model

Series

Parallel

9115 and 9115-AT

3 units (240 V Max)

3 units (180 A Max)

9116

2 units (300 V Max)

4 units (120 A Max)

Connecting more units in series/parallel than specified in the table above can cause

damage to the power supplies and void the manufacturer’s warranty.

Connection and Setup

Connecting multiple power supplies in parallel or in series can increase the overall current

output or voltage output respectively. For this configuration to function properly, there are

several items that must be set up first. Follow the instructions in this section carefully for setup.

Connection

Determine the total number of power supplies that you want to connect in parallel or series.

Disable the output of the power supplies and power OFF the power supplies.