6.7 Connecting Load Cables to TPL Circuitry
High Capacity
Connect TPL fuse holders to the load and the external return bus bar with up to 2x 750 MCM wire.
Low Capacity
Connect TPL fuse holders to the load and the external return bus bar with up to 350 MCM wire.
)LJXUH ² +LJKFDSDFLW\73/IXVHZLULQJVKRZQZLWK
2x 750 MCM wire)
6.7.1 TPL Fuse Alarm Control
The alarm board mounted on the inside front door of each distribution module has a DIP switch for disabling
alarms from unused TPL fuse locations. From the factory all switched are set to ON.
1. Disable TPL fuse alarms for unused TPL fuse positions. (Use the dip switch inside the distribution module
door —see Figure 12.)