-5HY%
6.5 Battery
Connections
Battery cables should be sized for a 0.25 V drop from battery to the power system at full load including antici-
pated growth. The cables should also meet ampacity requirements.
6.5.1 Battery Return Connections
Procedure:
1. Connect the battery return cables to an external battery return bus bar, if installed, (Figure 33) or to the return
bus bar termination on the bay:
([WHUQDO%DWWHU\5HWXUQ%XV%DU)LJXUH
%DWWHU\5HWXUQ7HUPLQDWLRQRQWKH%D\)LJXUH
•
24 sets of 1/2" holes on 1¾" centers
•
24 sets of 3/8" holes on 1" centers
•
72 sets of 1/4" holes on 3/8" centers
•
6 sets of 1/2" on 1 3/4" centers and/or
3/8" on 1" centers (12 if connected to both
sides of the bar)
2. In a two-bay system, balance battery and load returns evenly between the two bays.
)LJXUH ² ([WHUQDOEDWWHU\UHWXUQEXVEDUGXDOOHYHOVKRZQ
6.5.2 -48V Battery Cables
&$87,21
'R127PDNH¿QDOFRQQHFWLRQWREDWWHU\OLYH,QVXODWHDQGOHDYHGLVFRQQHFWHGRUUH
PRYHWKHEDWWHU\IXVHV6ZLWFKEDWWHU\FRQWDFWRUVRIILIXVHG
1. Connect directly to the -48V bus bar at the left top of the power system bay.
2. In a two-bay system, balance the quantity of batteries evenly between the two systems.
/LYH
5HWXUQ
/LYH
5HWXUQ
See Table E
on page 40 for
recommended
torque values.