-5HY%

5.6.3 Temperature Probe for Monitoring Battery Temperature

1. Connect CXC temperature probes from CXC to battery termination post negative, if applicable. Pick a good

location at mid-height on one or more battery string that will provide a good average temperature reading;
i.e., away from heating or cooling sources.