Alpha Technologies Te41, 24V User Manual
Page 5
Specifications for Argus’ Te41 Outdoor Power Enclosure
Argus Technologies Ltd.
029-029-B1 Rev B WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 1 of 2
Electrical
Input Voltage:
120/240Vac, 60Hz single phase
120Vac for auxiliary equipment
240Vac for rectifiers
AC Distribution Panel Options: Main breaker 22 KAIC rated
Main breaker 65 KAIC rated
Output Voltage:
24Vdc system
48Vdc system
Output Power:
34.1kW (11x Cordex 24V rectifiers; Argus #010-572-20)
24.8kW (8x Cordex 24V rectifiers; Argus #010-572-20) w/ 200A ac panel
32.4kW (9x Cordex 48V rectifiers; Argus #010-567-20)
25.2kW (7x Cordex 48V rectifiers; Argus #010-567-20) w/ 200A ac panel
18.0kW (10x Cordex 48V rectifiers; Argus #010-580-20)
Recommended Feeder Breakers (no integrated ac distribution panel)
Per rectifier (11 max.):
2-pole, 30A (240Vac single phase)
For internal load center:
1-pole, 30A (120Vac single phase)
Supplied Feeder Breakers (integrated ac distribution panel)
Per rectifier (8 max.):
2-pole, 30A (240Vac single phase)
For internal accessories:
1-pole, 15A (120Vac single phase)
Mechanical
Dimensions:
2134mm H x 762mm W x 762mm D
(84" H x 30" W x 30" D)
2134mm H x 1016mm W x 1067mm D w/ 200A ac panel
(84" H x 40" W x 42" D)
Weight:
453.5 kg (1000 lb.), no batteries, no rectifiers;
Example, maximum fully loaded with batteries and rectifiers: 924.3 kg (2038 lb.),
when using GNB 53.7 kg (118.4 lb.) batteries and 4.6 kg (10.1 lb.) rectifiers.
Mounting:
Pad or platform
Cooling:
Upper compartment is fan cooled (rectifiers and distribution)
Lower compartment is air conditioned (batteries and customer equipment)
Enclosure:
Aluminum, 5052-H32
Internal Rack:
23”, 7RU dedicated to customer equipment