11

HVAC Default Settings

Refer to the air conditioner manual (supplied with the system) for operation and maintenance details.

11.1 Air Conditioner/Heater Package

Description

Setting

Cooling System ON Temperature

80

qF [26.6qC]

Heating System ON Temperature

60

qF [15.5qC]

HVAC Fail Alarm

(e.g. by dirty filter or failed condensor)

300psi, reset at 225psi

11.2 Enclosure Temperature Alarms

Battery Compartment Thermostat

Setting

High Temperature Alarm (Blue)

35

qC (95qF)

Low Temperature Alarm (Red)

-15

qC (5qF)

Power Compartment Thermostat

Setting

High Temperature Alarm (Blue)

65

qC (149qF)

Low Temperature Alarm (Red)

-15

qC (5qF)

11.3 Cooling Fans

Fan speed is controlled electronically. At temperatures below 30

qC (86qF) they will shut off.