3accessories (options), 1 additional cordex rectifier shelf, 2 equipment mounting slides – Alpha Technologies Te41, 24V User Manual
Page 16: 3 battery shelves, 4 gmt fuse distribution
Argus Technologies Ltd.
057-102-C0 Rev B WC
Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 4 of 26
3
Accessories (Options)
3.1
Additional Cordex Rectifier Shelf
See Cordex rectifier manual included with the system documentation package.
3.2
Equipment Mounting Slides
Optional equipment mounting slides can be added to the system in the battery/customer equipment compartment.
Figure 4–Equipment mounting slide (2PL)
3.3
Battery Shelves
Battery shelves are designed to accommodate different battery manufacturers as shown in the following table:
Battery Manufacturer/Number
Height mm (in.)*
Width mm (in.)
Length mm (in.)
Weight kg (lb.)
GNB M12V155FT
283.2 (11.15)
124.5 (4.90)
558.8 (22.00)
53.98 (119.0)
Alpha SpaCell SMU-F 155
281.9 (11.10)
124.5 (4.90)
556.3 (21.90)
53.98 (119.0)
Alpha SpaCell SMU-F 170
309.9 (12.20)
124.5 (4.90)
556.3 (21.90)
58.88 (129.8)
East Penn 12AVR-150ET
298.5 (11.75)
124.5 (4.90)
558.8 (22.00)
52.16 (115.0)
C&D TEL12-150F
318.3 (12.53)
122.7 (4.83)
557.5 (21.95)
56.52 (124.6)
C&D TEL12-180F
320.0 (12.60)
125.7 (4.95)
533.7 (21.01)
59.42 (131.0)
Enersys 12V155FS
281.9 (11.10)
124.5 (4.90)
561.3 (22.10)
56.97 (125.6)
NSB 170
320.0 (12.60)
125.0 (4.92)
558.8 (22.00)
57.88 (127.6)
* 8RU typical
Table A–Battery manufacturers
Straps are used to secure batteries within the enclosure upon installation.
NOTE: Batteries will be shipped on a separate pallet and packaged per the manufacturers guidelines.
3.4
GMT Fuse Distribution
An optional 8-position GMT fuse block assembly provides DC power distribution for smaller customer equipment
mounted in the rack space. This will be located under the right side of the DC distribution in the power equipment
compartment.