5.

Connect wire cables to the main lugs located at the top, inside load center, as follows:
a.

Black to L1 (Line 1 connection),

b.

Red to L2 (Line 2 connection),

c.

White to N (to neutral connection on circuit breaker interior assembly neutral bus bar),

d.

Green or bare copper to equipment ground bar.

AC power input wiring terminal
lug connections

Circuit breaker interior assembly neutral
bus bar terminal lug connection

Equipment ground bar

L1

L2

N

Generator disconnect breaker

Main (utility) disconnect breaker

Figure 14–External AC load center connections

6.

Once all connections have been completed, close and tighten screws on deadfront cover.

6.3.3

Neutral-Ground Bonding

When the AC load center is used as a service entrance, the included N-G bonding kit should be installed per
instructions provided with the kit.

6.3.4

Automatic Transfer Switch (ATS)

See Figure 13 and the manual for the external AC load center included with the system documentation package.

6.3.5

PanLoc™ Generator Connection Panel

See images below and the manual for the external AC load center included with the system documentation
package.

Figure 15–PanLoc™ Generator Connection Panel

Inside of generator
connection panel

CAUTION

Failure to wire the
receptacle according to
the color code and
orientation, as shown in
the PanLoc™ Generator
Receptacle Mounting
Instructions, could
result in equipment
damage.

Front of generator
connection panel,
located on the left
side of the external
AC load center

(Illustration only and may not match your installation)