beautypg.com

Alpha Technologies Te41, 24V User Manual

Page 20

background image

Argus Technologies Ltd.

057-102-C0 Rev B WC

Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 8 of 26

5.4

Enclosure Mounting

See enclosed drawing for mounting hole layout.

5.4.1

Concrete Pad

Cast-in-place or pre-cast concrete slabs can be used. Install isolation pad to prevent moisture ingress.

Place the enclosure on the concrete slab and secure with Hilti HSL heavy-duty expansion anchor bolts or
approved equivalent. Secure the enclosure using the specific recommendations from the chosen fastener
manufacturer, taking into account the embedment depth and clear edge distances in order for the securing device
to achieve its full structural capacity. All alternates other than what is provided directly with the enclosure will need
to be reviewed by a registered professional engineer qualified to practice within the area where the enclosure is
being installed.

Alternate installation could be to use a chemical anchoring system such as Hilti HY150 for concrete or HY20 for
masonry along with suitable threaded rods and inserts from the same manufacturer. Spacing and placement
utilizing this method shall be performed as per the manufacturer’s recommendations.

5.4.2

Steel Platform

Install isolation pad to prevent dissimilar metal corrosion.

It is recommended that the mounting bolts be 1.27cm (1/2”) diameter A325 structural bolts in conjunction with a
backing plate/clasp to grip the underside of the grating. Once the enclosure is in place, secure on the inside using
appropriate washers and nuts.

5.5

Cable Bridge (Enclosure to Enclosure) Interface

The cable bridge interface installation kit can be mounted on either the left or right side of the enclosure.

NOTE: This kit must be installed prior to installing the adjacent enclosure.

See enclosed drawings for interface kit assembly.

Remove interface plate as required for cable routing. Also remove knockouts on lower rear side panels.

Apply gasket around opening used for cable routing.

For reduced cable
requirements, use half plate to
partially cover the opening