Specifications for Alpha Cordex HP 48-1.2kW 19" 1RU Shelf System w/CXCM1 &
GMT Distribution Modules
Apha Technologies Ltd.
030-851-B1 Rev B
Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.
Basic Unit, Shelf
Maximum total output current:
75 A
Maximum total output voltage:
58 Vdc
Maximum total output power:
3.6 kW
Maximum output current to load:
40 A
Maximum output current to battery:
70 A
Recommended Feeder Breaker
Single Phase:
120 V, 15 A, #14 AWG (per individual feed of two rectifiers)
240 V, 20 A, #12 AWG (per individual feed of two rectifiers)
Mechanical
Dimensions:
44 mm H x 439.5 mm W x 305 mm D (rectifier front panel 12.5mm D)
[1.75" H x 17.3" W x 12" D (rectifier front panel 0.49" D)]
Mounting*:
19" or 23" rack, center (5" or 6") or flush, EIA rack spacing
Weight:
3.0 kg (6.6 lb.)
Connections
AC Input:
2 x IEC-60320-C20 MAIC connectors
(for use with IEC-60320-C19 female line cords)
Chassis ground:
Via rack through mounting brackets and AC cords
Communications:
CAN (bus, single in/out) RJ-12 offset (female)
DC output to batteries:
1/4" holes with 5/8" centers, 70 A capacity
DC output to load:
7 x plug-in screw connector, 2-pos, 3.5 mm spacing, 8 A, 300 V, #30-16 AWG
1 x plug-in screw connector, 2-pos, 5 mm spacing, 10 A, 300 V, #26-14 AWG
Safety
EN 60950
Rectifier output shall be rated SELV suitable for connection to TNV-1 circuits
UL
60950-1-2002
CSA
60950-1-03
CE
EN 60950, CB Scheme
73/23/EEC Low Voltage Directive with amendment 93/68/EEC
Telcordia (Bellcore)
GR-1089-CORE (requirements applicable to rectifier)
* See drawings at the rear of this manual.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.